2 - 93
SIEMENS PC 3
(S5 PG port)
3 2
Connection
Connect to the S5 series PG port.
The communication parameter setting of ZM-** is done automatically.
Available PC
PC Link Unit
Wiring Diagram
(refer to P2-94)
S5 series
*[6ES5 734-1BD20] cable made by SIEMENS
+ RS-232C [Wiring Diagram 1]
Programing port
on a CPU unit
ZM-71SE
Model Setting
S5 PG port
* When using [6ES5 734-1BD20] cable made by SIEMENS, connect the cable of [Wiring
Diagram 1] to the D-sub 25 pins side of [6ES5 734-1BD20] to communicate with V6.
Available Memory
<E.g.> DB003000
Block No.
Address No.
Memory Bit Write TYPE Remarks
DB (data register) 0 Use memories more than DB3.
I (input relay) 1 IW as word device
Q (output relay) 2 QW as word device
F (internal relay) 3 FW as word device
T (timer/current value) 4
C (counter/current value) 5
AS (absolute address) 6
The assigned memory is indicated while editing the
screen as illustrated:
Available: Unavailable:
Set the memory to the extent of the memory range of each PC model. In case of using the [Bit Write] memory as the
bit device of the [Output Action] is [Momentary W], the other bits will be cleared when the bit memory is output,
because the [Bit Write] will be output by one word (refer to P5-10, reference 14-7 of ZM-71SE Instruction Manual).
Use [TYPE] number to assign indirect memory for macro programs.
Declare more than 1 word of DB3 (data register) in PLC side previ-
ously. If not so, ZM-** cannot communicate with this PLC. Also, it is necessary to declare DB to be used
in the software previously.
2 SIEMENS PC • 3