2 - 46
1 5
YOKOGAWA PC 2
(FA-M3)
Available PC
19200bps
Even
7
Provided
None (Fixed)
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit 1
Sumcheck
Terminal Character
Item Setting of PC
19200bps
Even
7
1
Comm. Parameter of ZM-
**
None (Fixed)
Protection Function
Communication Setting
FA-M3FA-M3
Programming tool port
*1
on a CPU module
PC Link Unit
Wiring Diagram
(refer to P2-48)
RS-232C [Wiring Diagram 1]
F3LC01-1N
*2
F3LC11-1N
RS-232C [Wiring Diagram 1]
F3LC11-2N
RS-422 [Wiring Diagram 2]
ZM-71SE
Model Setting
Cable made by YOKOGAWA
[KM11-2N]
Programming tool port
on a CPU module
Cable made by YOKOGAWA
[KM11-2N]
FA-M3 R
FA-M3R
*1 CPU types which can be connected directly to programming tool port on a CPU module are
"F3SP21-0N," "F3SP25-2N" and "F3SP35-5N."
*2 When the link unit, F3LC01-1N, is used, the communication setting and available memory are
the same as the contents of "14 YOKOGAWA PC 1(FA-500)," provided that B(common
register) cannot be used.
The recommended communication parameter setting of both PC and ZM-
**
is as follows:
2 YOKOGAWA PC • 2
* When using programming tool port on a CPU module for direct connection to ZM-**, set [Data
Length] as [8-bit] in the [comm. Parameter] dialog of ZM-** because data length 8 is fixed.
Also, specify the "CPU Communication Port" setting of "Configuration" in the ladder making tool
as follows.
Personal computer link function
: Use