2 - 54
TOYOPUC PC
Available PC
1 8
Communication Setting
19200bps
Even
7 (ASC II)
0
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit 2
Port
Item Setting of PC
19200bps
Even
2
Comm. Parameter of ZM-
**
0
7
Switch Setting
SW1
Switch
SW2
SW3
0
0
1
Setting Contents
Station address (lower half)
Station address (upper half)
Baud rate
1 : 19200 2 : 9600 3 : 4800
4 : 2400 5 : 1200 6 : 600
SET2
Switch
SET3
Provided
Provided
Short bar
Contents
Data bit 7
Stop bit 2
PC Link Unit
Wiring Diagram (refer to P2-56)
TOYOPUC-L2/PC2 etc. CMP-LINK
RS-422 [Wiring Diagram 1]
ZM-71SE
Model Setting
TOYOPUC
Baud rate: 19200bps
The recommended communication parameter setting of both PC and ZM-
**
is as follows:
2 TOYOPUC PC
Set the [Trans. Mode] for [Detail] in the [Comm. Parameter]of the ZM-71SE.
· PC3J : Select [Single Data Area] or [Split Data Area].
· L2/PC2 series : Select [Single Data Area].
Trans. Mode Contents
Single Data Area Data area is common.
Split Data Area Divide each PLC device into a program file.