Table 6.12 IAQ strategies for rotating heat exchangers
Design Operation
Select a wheel equipped with purging
sector and install it with the purging
sector on the warm side of the wheel
Supply and exhaust fans should be located
and sized so that a positive pressure
difference of about 200 Pa is achieved
between supply and exhaust ducts at the
wheel level
Avoid hygroscopic wheels when
contamination is an important concern
Change wheels if they are warped
Install filters in both channels upwind of
the heat exchanger
If pressure on supply side is negative
compared to exhaust side then change
pressure hierarchy
If the rotation of wheel is in the wrong
direction then change to proper direction:
the wheel should pass from exhaust to
supply ducts in front of the purging sector
Clean dirty wheels according to
instructions of the manufacturer, with
either compressed air, vacuu m cleaner or
pressurized water
Check that the wheel control stops the
wheel when no heat can be recovered
Table 6.13 IAQ strategies for humidifiers
Design Operation
Prevent pollution from water, water tanks and devices/agents to disin fect, demineralize
and/or desalinate the water
Remove oil residue before use of
humidifier to prevent an oil film on water
Take care using disinfecting material
Use UV as germicide
De-ionization cartridges to prepare soft
water might emit VOCs
Install demineralization device in disperser
to keep the oscillator circuit board free
from mineral precipitation for as long as
possible
If there is an oil film on water surface,
drain water and clean humidifier
immediately
Change water every week
Clean tank (not possible for steam: keep
them dry/empty when not in use)
Clean humidifier regularly every six
months (dry or wet)
Desalinization must take place with an
agent that does not smell
Use a control system with which
Humidifier should automatically shut
down when the HVAC system is off
New water is added when the water
temperature exceeds 208C (spray nozzle
and evaporative humidifiers, ultrasonic
humidifiers)
Check operation of control system
regularly
Other recommendations
Do not use porous wet material
Prevent condensation from steam
humidifier
130 Ventilation and Airflow in Buildings