Leakage through heat exchangers
Some heat exchangers let some air leak between both air channels. This is in
most cases not expected, since there are very few air handling units equipped
with both recirculation and a heat exchanger. In addition, some air is entrained
by the rotation of the wheel in rotating heat exchangers. The amount of air
transferred this way can be measured with tracer gases (see Chapter 2, ‘Airflow
measurements at ventilation grilles’), and the leakage flow rate is one of the
results of the measurement of airflow rates in the air handling unit.
As mentioned in Chapter 2, the glob al recirculation rate can easily be
checked by measur ing the concentration of a tracer injected in the ventilated
space, such as the carbon dioxide exhaled by occupants. Assuming that there
is no inverse recirculation and no leaks in the air handling unit, the global
recirculation rate is:
R ¼
C
supply
C
outdoor
C
exhaust
C
outdoor
ð5:14Þ
If no recirculation is expected, but a significant recirculation rate is observed, it
may be the result of leakage through the heat exchanger. If more information is
required, in particular to check whether it is the exchanger or another part of
the air handling unit that leaks, additional measurements could be performed,
as described in Chapter 2, ‘Airflow rate measurements in air handing units’.
Pressure differential measurements are useful to explain leakage. In addi-
tion, these are easier to perform than leakage measurements and can readily
bring information for a diagnosis. Pressure differentials should be measured
between the following locations (see Figure 5.7):
.
Between one and six on one hand, and three and four on the other hand.
These pressure differentials drive the leakage direction. They should be
zero or slightly posi tive, so that a possible leakage flow goes from supply
to exhaust, and not the contrary.
.
Between one and three on one hand, and four and six on the other hand.
These pressure differentials increase with clogging. Compare them with
the nominal pressure differential gi ven by the factory for the actual airflow
4
Exhaust air
Outdoor air
Supply air
Extract air
- +
31
6
Figure 5.7 Schematics of an air handling unit, showing locatio n of
pressure taps for pressure differential measurements
88 Ventilation and Airflow in Buildings
Zobrazit stránku 108
1 2 ... 104 105 106 107 108 109 110 111 112 113 114 ... 210 211

Komentáře k této Příručce

Žádné komentáře

American Dynamics ULTRA VIIE manuales

Manuales del propietario y guías del usuario para Cámaras De Seguridad American Dynamics ULTRA VIIE.
Ofrecemos 5 manuales en pdf American Dynamics ULTRA VIIE para descargar gratis por tipos de documentos: Manual de usuario, Manual del operador, Guía de instalación






Más productos y manuales para Cámaras De Seguridad American Dynamics

Modelos Tipo de documento
RAS917LS-1 Especificaciones   American Dynamics RAS917LS-1 Specifications [de] [en] [fr] [it] , 41 paginas
RAS916LS-1 Manual de usuario   Guía de instalación y funcionamiento, 126 paginas
RAS916 Manual de usuario   DX4500/DX4600 Series Digital Video Recorder, 4 paginas
ADC860 Especificaciones       American Dynamics ADC860 Specifications, 92 paginas
RAS918LSP Manual de usuario   SpeedDome® Ultra VII Day/Night, 4 paginas
RAS917LS-1 Manual de usuario   SpeedDome® Ultra VII Tag/Nacht, 4 paginas
SpeedDome Optima LT Manual del operador   American Dynamics SpeedDome Optima LT Operator`s manual, 8 paginas
ADCA330CN Manual de usuario   subasta de walmart jueves 16 de enero del 2014, 2 paginas
RAS917LS-1 Especificaciones   American Dynamics RAS917LS-1 Specifications [en] [fr] , 40 paginas