simultaneously the r.m.s. voltage, U, between phase and neutral point, the
r.m.s. current, I, running into each motor coil and the phase shift, , between
voltage and current. The power is calculated by:
e
¼
X
3
j ¼1
U
j
I
j
cosð
j
Þð5:54Þ
the sum being on all three phases.
In very small air handling units, the fan motor may be single phase, and
e
¼ UI cosðÞð5:55Þ
To measur e the current an ampere-meter must be installed in the circuit. An
easy way is to use clamp-on ampere-meters. A measuring clamp is installed
around each wire leading to the motor. This clamp contains a transformer
that gives a current proportional to the current running through the closed
clamp. Care should be taken not to install the clamp around the two -wire or
four-wire cable. The measured current will be zero in this case, whatever the
power used by the motor.
In some air handling units, the fan is controlled by a variable frequency
controller (see Figure 5.15). Such devices are often equipped with a screen
Figure 5.15 Front panel of the variable frequency controller
Measurements and Measures Related to Energy Efficiency in Ventilation 101